| Standby Rating | kVA | 27 |
| Standby Rating | kW | 21,6 |
| Prime Rating | kVA | 25 |
| Prime Rating | kW | 20 |
| Frequency | Hz | 50 |
| Voltage | V | 230/400 |
| Fuel Type | Diesel | |
| Control Panel Model | Datakom D309 | |
| Cabin | AK 10 |
| Brand | CUMMINS | |
| Model | X2.5G2 | |
| Engine Type | 4 Stroke – Diesel | |
| Injection Type | Direct Injection | |
| Suction System | Natural | |
| Number of Cylinders | 3 | |
| Cylinder Diameter and Stroke | mm | 91,4×127 |
| Cylinder Volume | L | 2,5 |
| Cooling Type | Water Cooled | |
| Fuel Consumption at Stand by Load | l/h | 6,5 |
| 100% Fuel Consumption at Prime Load | l/h | 6 |
| 75% Fuel Consumption at Prime Load | l/h | 4,8 |
| 50% Fuel Consumption at Prime Load | l/h | 3,5 |
| Total Oil Capacity | L | 6,5 |
| Total Cooling Capacity | L | 5,5 |
| Governor Type | Type | Electronic |
| Brand | Leroy Somer | |
| Model | TAL-A42-C/TAL-042-C | |
| Output Voltage | V | 230/400 |
| Frequency | HZ | 50 |
| Automatic Voltage Regulation | ±% | 1 |
| Alternator Standby Power | kVA | 33 |
| Alternator Continuous Use Power | kVA | 30 |
| Power Factor | Cosq | 0,8 |
| Number of Cables | 12 | |
| Winding Pitch | 2/3 | |
| Protection Class | IP23/H | |
| Warning System | Self-excited | |
| Execution System | Electronic AVR | |
| Performance – PF 0.8 / 75% Load | % | 86,5 |
Dimensions Without Canopy and Weight |
||
| Length x Width x Height | mm | 1770x850x1440 |
| Net Weight | kg | 950 |
| Fuel Tank Capacity | lt | 135 |
Dimensions With Canopy and Weight |
||
| Length x Width x Height | mm | 2225x950x1660 |
| Net Weight | kg | 1010 |
| Fuel Tank Capacity | lt | 135 |
| Desibel | db(A) | 65-75 |




Reviews